As Crouse-Hinds series MTL products become obsolete, Eaton offers as many options for a replacement product as possible. This information can be found by searching for the obsolete product by part number listing below.
Disclaimer: Every effort has been made to ensure the accuracy of this information. Eaton recommends verification of the information necessary to make the appropriate product selection and the safety calculation for a given application.
Information in this cross reference is subject to change without prior notice.
Please select the product group from the listing below:
| Earlier / Obsolete Products | Nearest Equivalent Product | Comments |
| MTL101 | No equivalent | Low voltage AC or DC systems |
| MTL102 | No equivalent | Low voltage AC or DC systems |
| MTL103 | No equivalent | Low voltage AC or DC systems |
| MTL105 | MTL7755AC | Convert to DIN-rail mount |
| MTL110 | MTL7710+ | Convert to DIN-rail mount, +ve only |
| MTL115 | MTL7715+ | Convert to DIN-rail mount, +ve only |
| MTL122 | MTL7722+ | Convert to DIN-rail mount, +ve only |
| MTL128 | MTL7728+/-/AC | Convert to DIN-rail mount, check polarity |
| MTL129 | No equivalent | — |
| MTL151 | No equivalent | For THC with moving coil instruments |
| MTL152 | No equivalent | For THC with moving coil instruments |
| MTL155 | MTL7755AC | Convert to DIN-rail mount |
| MTL156 | MTL7755AC | Convert to DIN-rail mount, check working voltage |
| MTL160 | MTL7760AC | Convert to DIN-rail mount, check working voltage |
| MTL161 | MTL7761AC | Convert to DIN-rail mount, check working voltage |
| MTL164 | MTL7764AC | Convert to DIN-rail mount, no -ve version, check working voltage |
| MTL165 | MTL7765AC | Convert to DIN-rail mount |
| MTL166 | MTL7766AC | Convert to DIN-rail mount |
| MTL172 | — | Contact us |
| MTL178 | MTL7778AC | Convert to DIN-rail mount |
| MTL179 | MTL7779+ | Convert to DIN-rail mount, no -ve version |
| MTL186 | — | Contact us |
| MTL187 | MTL7787+ | Convert to DIN-rail mount |
| MTL188 | MTL7788+ | Convert to DIN-rail mount |
| MTL188R | MTL7788R+ | Convert to DIN-rail mount |
| Earlier / Obsolete Products | Nearest Equivalent Product | Comments |
| MTL611 | No equivalent | Psion based and Psion stopped making it |
| MTL611B | No equivalent | Psion based and Psion stopped making it |
| MTL633 | MTL661/662 | Depends on mounting arrangement; MTL661 surface or pipe; MTL665 panel |
| MTL633B | MTL661/662 | Non-ATEX; depends on mounting arrangement; MTL661 surface or pipe. MTL665 panel |
| MTL634 | MTL661/662 | Non-ATEX; depends on mounting arrangement; MTL661 surface or pipe. MTL665 panel |
| MTL636 | No equivalent | Depends on application |
| MTL637 | No equivalent | — |
| MTL642 | MTL646/647 | Depends on mounting required |
| MTL643 | MTL647 | Field replacement units have the same or more functionality, but are of different physical shape |
| MTL644 | MTL646 | Panel |
| MTL650 series | No equivalent | — |
| MTL670 series | No equivalent | — |
| MTL681B | MTL661 | Original units non-ATEX |
| MTL682B | MTL661 | Original units non-ATEX |
| MTL683B | MTL665 | Original units non-ATEX |
| MTL684B | MTL665 | Original units non-ATEX |
| MTL686 | MTL661 | Original units non-ATEX |
| MTL688 | MTL665 | Original units non-ATEX |
| Earlier / Obsolete Products | Nearest Equivalent Product | Comments |
| MTL7000 | MTL7700 range | Refer to Baseefa compatibility cross reference SCI946 |
| MTL702+ | MTL706+ | MTL702+ not fully CE compliant; MTL706+ is the functional equivalent, but has a different safety description |
| MTL706+ | MTL7706+ | — |
| MTL707+ | MTL7707+ | — |
| MTL707P+ | MTL7707P+ | — |
| MTL708+ | — | Contact us |
| MTL710- | — | Contact us |
| MTL710+ | MTL7710+ | — |
| MTL710AC | — | Contact us |
| MTL710P- | — | Contact us |
| MTL710P+ | — | Contact us |
| MTL715- | — | Contact us |
| MTL715+ | MTL7715+ | — |
| MTL715P+ | MTL7715P+ | — |
| MTL722 - | — | Contact us |
| MTL722+ | MTL7722+ | — |
| MTL722P+ | — | Contact us |
| MTL728- | MTL7728- | — |
| MTL728+ | MTL7728+ | Convert to DIN-rail mount |
| MTL728AC | MTL7728AC | — |
| MTL728P+ | MTL7728P+ | — |
| MTL729P+ | MTL7729P+ | — |
| MTL751AC | — | Contact us |
| MTL755AC | MTL7755AC | — |
| MTL758- | MTL7758 - | — |
| MTL758+ | MTL7758+ | — |
| MTL760AC | MTL7760AC | — |
| MTL761AC | MTL7761AC | — |
| MTL761PAC | MTL7761PAC | — |
| MTL764- | — | Contact us |
| MTL764+ | MTL7764+ | — |
| MTL764AC | MTL7764AC | — |
| MTL765AC | MTL7765AC | — |
| MTL766AC | MTL7766AC | — |
| MTL766PAC | MTL7766PAC | — |
| MTL767- | — | Contact us |
| MTL767+ | MTL7767+ | — |
| MTL768- | — | Contact us |
| MTL768+ | — | Contact us |
| MTL772AC | — | Contact us |
| MTL778AC | MTL7778AC | — |
| MTL779- | — | Contact us |
| MTL779+ | MTL7779+ | — |
| MTL786+ | MTL7789+ | — |
| MTL787- | MTL7787- | — |
| MTL787+ | MTL7787+ | — |
| MTL787S+ | MTL7787+ | — |
| MTL787SP+ | MTL7787P+ | — |
| MTL788- | — | Contact us |
| MTL788+ | MTL7788+ | — |
| MTL788R- | — | Contact us |
| MTL788R+ | MTL7788R+ | — |
| MTL791 | — | Contact us |
| MTL796- | MTL7796- | — |
| MTL796+ | MTL7796+ | — |
| MTL799 | MTL7799 | — |
| Earlier / Obsolete Products | Nearest Equivalent Product | Comments |
| MTL2210B-120V | MTL5511 + MPA5500 | MTL5511 does not have stop/start feature of the MTL2210B and only has one contact output. Use MTL5510B for start/stop, but check the load voltage and current requirements against the MTL5510B specification. An interposing relay may be required for some applications. |
| MTL2210B-240V | MTL5511 + MPA5500 | MTL5511 does not have stop/start feature of the MTL2210B and only has one contact output. Use MTL5510B for start/stop, but check the load voltage and current requirements against the MTL5510B specification. An interposing relay may be required for some applications. |
| MTL2210B-24DC | MTL5511 | MTL5511 does not have stop/start feature of the MTL2210B and only has one contact output. Use MTL5510B for start/stop, but check the load voltage and current requirements against the MTL5510B specification. An interposing relay may be required for some applications. |
| MTL2211-120V | MTL5516C + MPA5500 | — |
| MTL2211-240V | MTL5516C + MPA5500 | — |
| MTL2211-24DC | MTL5516C | — |
| MTL2212-120V | MTL5516C + MPA5500; two required | The MTL2212 was a 3-channel DI unit; the MMTL5516C+MPA5500 is a 2-channel unit |
| MTL2212-240V | MTL5516C + MPA5500; two required | The MTL2212 was a 3-channel DI unit; the MTL5516C+MPA5500 is a 2-channel unit |
| MTL2212-24DC | MTL5516C; two required | The MTL2212 was a 3-channel DI unit; the MTL5516C is a 2-channel unit |
| MTL2213-120V | MTL5516C + MPA5500; two required | The MTL2213 was a 3-channel DI unit; the MTL5516C+MPA5500 is a 2-channel unit |
| MTL2213-240V | MTL5516C + MPA5500; two required | The MTL2213 was a 3-channel DI unit; the MTL5516C+MPA5500 is a 2-channel unit |
| MTL2213-24DC | MTL5516C; two required | The MTL2213 was a 3-channel DI unit; the MTL5516C is a 2-channel unit |
| MTL2215-120V | MTL5526 + MPA5500 | — |
| MTL2215-240V | MTL5526 + MPA5500 | — |
| MTL2215-24DC | MTL5526 | — |
| MTL2220-120V | No equivalent | — |
| MTL2220-240V | No equivalent | — |
| MTL2220-24DC | No equivalent | — |
| MTL2241-120V | MTL5525 + MPA5500 | Could also use the MTL5521 or MTL5524 (depends on safety description plus MPA5500) |
| MTL2241-240V | MTL5525 + MPA5500 | Could also use the MTL5521 or MTL5524 (depends on safety description plus MPA5500) |
| MTL2241-24DC | MTL5525 | Could also use the MTL5521 or MTL5524 (depends on safety description of field equipment) |
| MTL2242-120V | No equivalent | Only option would be to use a single channel unit (MTL5524 plus MPA5500) |
| MTL2242-240V | No equivalent | Only option would be to use a single channel unit (MTL5524 plus MPA5500) |
| MTL2242-24DC | No equivalent | Only option would be to use a single channel unit (MTL5524) |
| MTL2313A-120V | MTL5314 + PSG60E24RM | The MTL5314 has two trip points as standard, not one as the MTL2313A |
| MTL2313A-240V | MTL5314 + PSG60E24RM | The MTL5314 has two trip points as standard, not one as the MTL2313A |
| MTL2313A-24DC | MTL5314 | The MTL5314 has two trip points as standard, not one as the MTL2313A |
| MTL2313B-120V | MTL5314 + PSG60E24RM | — |
| MTL2313B-240V | MTL5314 + PSG60E24RM | — |
| MTL2313B-24DC | MTL5314 | — |
| MTL2314A-120V | MTL5575 + MTL5314 + PSG60E24RM | THC trip amplifier. Note MTL5575 to be ranged by customer. |
| MTL2314A-240V | MTL5575 + MTL5314 + PSG60E24RM | THC trip amplifier. Note MTL5575 to be ranged by customer. |
| MTL2314A-24DC | MTL5575 + MTL5314 | THC trip amplifier. Note MTL5575 to be ranged by customer. |
| MTL2314B-120V | MTL5575 + MTL5314 + PSG60E24RM | THC trip amplifier. Note MTL5575 to be ranged by customer. |
| MTL2314B-240V | MTL5575 + MTL5314 + PSG60E24RM | THC trip amplifier. Note MTL5575 to be ranged by customer. |
| MTL2314B-24DC | MTL5575 + MTL5314 | THC trip amplifier. Note MTL5575 to be ranged by customer. |
| MTL2315A-120V | MTL5575 + MTL5314 + PSG60E24RM | RTD trip amplifier. Note MTL5575 to be ranged by customer. |
| MTL2315A-240V | MTL5575 + MTL5314 + PSG60E24RM | RTD trip amplifier. Note MTL5575 to be ranged by customer. |
| MTL2315A-24DC | MTL5575 + MTL5314 | RTD trip amplifier. Note MTL5575 to be ranged by customer. |
| MTL2315B-120V | MTL5575 + MTL5314 + PSG60E24RM | RTD trip amplifier. Note MTL5575 to be ranged by customer. |
| MTL2315B-240V | MTL5575 + MTL5314 + PSG60E24RM | RTD trip amplifier. Note MTL5575 to be ranged by customer. |
| MTL2315B-24DC | MTL5575 + MTL5314 | RTD trip amplifier. Note MTL5575 to be ranged by customer. |
| MTL2316-120V | No equivalent | Earth bonding monitor |
| MTL2316-240V | No equivalent | Earth bonding monitor |
| MTL2316-24DC | No equivalent | Earth bonding monitor |
| MTL2441B-120V | MTL5541 + MPA5500 | MTL5541 will handle HART comms as well |
| MTL2441B-240V | MTL5541 + MPA5500 | MTL5541 will handle HART comms as well |
| MTL2442B-120V | MTL5546Y + MPA5500 | MTL5546 will handle HART comms as well |
| MTL2442B-240V | MTL5546Y + MPA5500 | MTL5546 will handle HART comms as well |
| Earlier / Obsolete Products | Nearest Equivalent Product | Comments |
| MTL3011 | MTL5511 | — |
| MTL3012 | MTL5513 | Note the MTL5513 is a 2-channel device |
| MTL3013 | MTL5516C | — |
| MTL3014 | MTL5514D | — |
| MTL3021 | MTL5525 | — |
| MTL3022 | MTL5522 | MTL3022 has 75mA max. output; the MTL5522 has 70mA max. output |
| MTL3041 | MTL5541 | — |
| MTL3042 | No equivalent | May be able to use the MTL5546, but this needs 24 VDC supply |
| MTL3043 | MTL5561 | Note the MTL5561 has 2 channels, where the MTL3043 had 1 channel |
| MTL3045 | MTL5546 | — |
| MTL3046B | MTL5541 | — |
| MTL3047 | No real equivalent | — |
| MTL3052 | No equivalent | MTL831B/MTL3052/MTL838B replaced by MTL831C/MTL5553/MTL838C |
| MTL3054 | No equivalent | The MTL8800 block I/O is being terminated and this was the only function for the MTL3054 |
| MTL3055 | No equivalent | The MTL8800 block I/O is being terminated and this was the only function for the MTL3055 |
| MTL3056 | MTL5051 | — |
| MTL3057 | MTL5051 | — |
| MTL3058 | MTL5051 | — |
| MTL3059 | MTL5051 | — |
| MTL3071 | MTL5575 | The MTL3071 was mV to 4-20mA loop powered. The MTL5575 needs 24 VDC supply and has to be configured by the customer. |
| MTL3072 | MTL5575 | The MTL3071 was RTD to 4-20mA loop powered. The MTL5575 needs 24 VDC supply and has to be configured by the customer. |
| MTL3073 | MTL5575 | Note the MTL5575 needs to be configured by the customer |
| MTL3081 | MTL5081 | — |
| MTL3099 | MTL5599 | — |
| MTL3991 | PSG60E24RM | See MTL5500 section for details |
| MTL3992 | No equivalent | Used with strain gauges; no replacement |
| Earlier / Obsolete Products | Nearest Equivalent Product | Comments |
| MTL4013 | MTL4513 | — |
| MTL4014 | MTL4504 | Phase reversal added |
| MTL4015 | MTL4511 | No repeat contact on MTL4511; use MTL4510B if required; check connections on terminals 7 & 9 |
| MTL4016 | MTL4516 | No repeat contact on MTL4516; use MTL4510B if required |
| MTL4017 | MTL4517 | Phase reversal added; LFD relay phased reversed |
| MTL4021 | MTL4524 | Note change in part number scheme |
| MTL4021S | MTL4524S | Note: control input MUST be isolated from supply lines; check compatibility |
| MTL4023 | MTL4523 | — |
| MTL4023R | MTL4523R | — |
| MTL4024 | MTL4521L | Note change in part number scheme |
| MTL4024R | No direct equivalent | — |
| MTL4025 | MTL4525 | — |
| MTL4031 | MTL4531 | MTL4531 now works with 2-wire probes |
| MTL4032 | MTL4532 | — |
| MTL4041B | MTL4541B | — |
| MTL4041P | MTL4541P | Only intended for backward compatibility; P version not usually required on new projects |
| MTL4041T | MTL4541T | — |
| MTL4042 | No equivalent | Check use of MTL4541P |
| MTL4043 | No equivalent | MTL4541S may be suitable for some applications. Consult MTL technical support for clarification. |
| MTL4044 | MTL4544B | — |
| MTL4044D | MTL4544D | Check safe side connections |
| MTL4045B | MTL4546 | Handles HART as well |
| MTL4045C | MTL4546Y | Handles HART as well |
| MTL4045S | No equivalent | — |
| MTL4046 | MTL4546 | — |
| MTL4046C | MTL4546Y | — |
| MTL4048 | No equivalent | — |
| MTL4051 | No equivalent | LLMUX isolator - contact Honeywell |
| MTL4053 | MTL5553 | DIN-rail required |
| MTL4061 | MTL4561 | — |
| MTL4073 | MTL4573 | — |
| MTL4081 | MTL4581 | — |
| MTL4083 | No equivalent | — |
| MTL4099 | MTL4599 | — |
| MTL4099N | MTL4599N | — |
| MTL4215 | MTL4526 | — |
| MTL4216 | MTL4526 | — |
| MTL4220 | No equivalent | — |
| MTL4401 | No equivalent | — |
| MTL4403 | No equivalent | — |
| MTL4421RS | MTL4526 | Check relay rating |
| MTL4427-SR | No equivalent | Triconex special |
| MTL4927 | No equivalent | Triconex special |
| Earlier / Obsolete Products | Nearest Equivalent Product | Comments |
| MTL4706+ | 2 x MTL7706+ | DIN-rail mounting, not backplane mounting |
| MTL4715+ | 4 x MTL7715+ | DIN-rail mounting, not backplane mounting |
| MTL4728- | 4 x MTL7728- | DIN-rail mounting, not backplane mounting |
| MTL4728+ | 4 x MTL7728+ | DIN-rail mounting, not backplane mounting |
| MTL4755AC | MTL7756AC | DIN-rail mounting, not backplane mounting |
| MTL4760AC | 2 x MTL7760AC | DIN-rail mounting, not backplane mounting |
| MTL4763PAC | 1 x MTL7766AC; 2 x MTL7761PAC | DIN-rail mounting, not backplane mounting |
| MTL4778AC | 2 x MTL7778AC | DIN-rail mounting, not backplane mounting |
| MTL4781+ | 2 x MTL7789+ | DIN-rail mounting, not backplane mounting |
| MTL4787+ | 2 x MTL7787+ | DIN-rail mounting, not backplane mounting |
| MTL4787P+ | 2 x MTL7787P+ | DIN-rail mounting, not backplane mounting |
| MTL4788+ | 2 x MTL7788+ | DIN-rail mounting, not backplane mounting |
| MTL4788R+ | 2 x MTL7788R+ | DIN-rail mounting, not backplane mounting |
| MTL4796- | 2 x MTL7796- | DIN-rail mounting, not backplane mounting |
| Earlier / Obsolete Products | Nearest Equivalent Product | Comments |
| MTL5011B | MTL5511 | — |
| MTL5012 | — | Use 1ch of MTL5513 |
| MTL5012S | — | No replacement |
| MTL5014 | MTL5514/14D | MTL5514 does not provide 1-in 2-out function; MTL5514D with 1-in 2-out LFD relay energizes alarm |
| MTL5015 | MTL5513 | Common connection on haz. side; max. frequency response 500 Hz |
| MTL5016 | MTL5516C | — |
| MTL5017 | MTL5517 | LFD relay energizes on alarm |
| MTL5018 | MTL5516C | Common connection on haz. side |
| MTL5018ac | MTL5516C + MPA5500 | Common connection on haz. side |
| MTL5021 | MTL5521 | (12.8V. 48mA. cl 48mA) |
| MTL5022 | MTL5522 | (9.9V. 70mA. cl 70mA) |
| MTL5023 | MTL5523(V) | (12.8V. 48mA. cl 48mA); use 23V if phase link was fitted |
| MTL5024 | MTL5524 | (12.8V. 48mA. cl 48mA) |
| MTL5025 | MTL5525 | (7V. 48mA. cl 48mA). lower Io |
| MTL5031 | MTL5531 | Now Velometer compatible |
| MTL5032 | MTL5532 | Now with 4-20mA output and alarm |
| MTL5040 | — | Use MTL5541 and MTL5546Y |
| MTL5041 | MTL5541 | — |
| MTL5042 | MTL5541 | — |
| MTL5043 | MTL5544D | No current sink o/p. Passive Tx input |
| MTL5044 | MTL5544 | Now with passive Tx inputs |
| MTL5045 | MTL5546Y | Smart only versions |
| MTL5046 | MTL5546 | — |
| MTL5049 | MTL5549Y | Smart only versions |
| MTL5051 | — | — |
| MTL5053 | MTL5553 | — |
| MTL5061 | MTL5561 | — |
| MTL5073 | MTL5573 | — |
| MTL5074 | MTL5573 | — |
| MTL5081 | MTL5581 | — |
| MTL5082 | MTL5582 or MTL5582B | — |
| MTL5113P | MTL5501-SR | — |
| MTL5314 | — | Continues as MTL5314 model |
| MTL5344 | — | Discontinued |
| MTL5349 | — | Discontinued |
| MTL5533 | MTL5531; two required | — |
| MTL5991 | PSG60E24RM | — |
| MTL5995 | F101-PS | — |
| Earlier / Obsolete Products | Nearest Equivalent Product | Comments |
| MTL7000 | MTL7700 range | Refer to Baseefa compatibility cross reference SCI946 |
| Earlier / Obsolete Products | Nearest Equivalent Product | Comments |
| F600A-** | F880-2-** | MTL redundant fieldbus power supplies |
| F600A-C*-** | No equivalent | F600A carrier |
| F600A-CA | No equivalent | F660A IOTA, unpopulated |
| F610A | F810A-2P* | MTL redundant fieldbus power supplies |
| F610A | F810A-2P* | MTL redundant fieldbus power supplies |
| F610A-CL | No equivalent | F610A baseplate |
| F618D | F810A-2-P* | MTL redundant fieldbus power supplies |
| F618D-CL | No equivalent | F618D baseplate |
| F650A-CL-PS | No equivalent | F650A carrier, screw terminals |
| F650A-LS | No equivalent | F650A system - 2-segment |
| F660A | F860 | MTL redundant fieldbus power supplies |
| F660A-ALM | No equivalent | Alarm module |
| F690A-** | F890-2-P* | MTL redundant fieldbus power supplies |
| F690A-C*-** | No equivalent | F690 carrier |
| F880-RT | 9188 | MTL redundant fieldbus power supplies |
| Earlier / Obsolete Products | Nearest Equivalent Product | Comments |
| E02002-00301310 | E02002-10311310 | Use IS version; alternative offers square root extraction option |
| E02002-10300220 | E02002-10300221 | Alternative offers in/out monitor (monitors the deviation between input and output signal) |
| E02002-10300310 | E02002-10311310 | Alternative offers square root extraction option and live zero monitor (checks if the analogue signal for 0% is at 4 mA and not at 0 mA (line break monitor)) |
| E02002-10301210 | E02002-10311210 | Alternative offers square root extraction option |
| E02002-10301230 | E02002-20311331 | Check Uo-Io (IS parameters may be different - please check); alternative offers square root extraction option - HART |
| E02002-20300330 | E02002-20311331 | Alternative offers square root extraction option and live zero- in/out monitor (monitors the deviation between input and output signal) |
| E02002-20301330 | E02002-20311331 | Alternative offers square root extraction option and live zero monitor (checks if the analogue signal for 0% is at 4 mA and not at 0 mA (line break monitor)) |
| E02002-20311330 | E02002-20311331 | Alternative offers in/out monitor (monitors the deviation between input and output signal) |
| E02007-00312 | E02007-30312 | Use IS version |
| E02007-00332 | E02007-40332 | Use IS version |
| E02007-30311 | E02007-30312 | Use 2ch device |
| E02007-30312-E1 | E02007-30312 | Service with voltage input version |
| E02007-40311 | E02007-40312 | Use 2ch device |
| E02007-40341 | E02007-40342 | Use 2ch device |
| E02008-00302002 | E02008-40312102 | Use IS version; alternative offers repeater function as well as TX power supply option |
| E02008-00311101 | E02008-40311101 | Use IS version |
| E02008-00312001 | E02008-40312001 | Use IS version |
| E02008-30301001 | E02008-40311001 | Check Uo-Io (IS parameters may be different - please check); alternative offers repeater function as well as TX power supply option |
| E02008-30311001 | E02008-40311001 | Check Uo-Io (IS parameters may be different - please check) |
| E02008-30311001-S2 | E02008-40311001 | Check Uo-Io (IS parameters may be different - please check); signal range 4...20 mA only |
| E02008-30311101 | E02008-40311101 | Check Uo-Io (IS parameters may be different - please check) |
| E02008-30311101-S1 | E02008-40311001 | Check Uo-Io (IS parameters may be different - please check); signal range 4...20 mA only |
| E02008-30311111 | E02008-40311101 | Check Uo-Io (IS parameters may be different - please check); alternative: no power monitor (separate signal to monitor the card's power supply) |
| E02008-30312001 | E02008-40312001 | Check Uo-Io (IS parameters may be different - please check) |
| E02008-30312101 | E02008-40312101 | Check Uo-Io (IS parameters may be different - please check) |
| E02008-30312111 | E02008-40311101 | Check Uo-Io (IS parameters may be different - please check); alternative: no power monitor (separate signal to monitor the card's power supply) |
| E02008-30612101 | E02008-40312101 | Check Uo-Io (IS parameters may be different - please check); alternative: no AC power |
| E02008-30612111 | E02008-40312101 | Check Uo-Io (IS parameters may be different - please check); alternative: no AC and power monitor (separate signal to monitor the card's power supply) |
| E02008-40302002 | E02008-40312102 | Alternative offers repeater function as well as TX power supply option |
| E02009-003020 | E02009-303020 | Use IS version |
| E02009-003121S | E02009-403121S | Use IS version |
| E02009-013010S | E02009-313110 | Use IS and repeater only option |
| E02009-203020 | E02009-303020 | Check Uo-Io (IS parameters may be different - please check) |
| E02009-203111 | E02009-203121 | Use 2ch device |
| E02009-203111S | E02009-203121 | Use 2ch device - no switch available to set to repeater function |
| E02009-203121S | E02009-203121 | No switch available to set to repeater function |
| E02009-403020 | E02009-303020 | Check Uo-Io (IS parameters may be different - please check) |
| E02009-403121 | E02009-403121S | Alternative offers switch to set to repeater function |
| E02010-00302110 | E02010-30312111 | Use IS version; alternative offers live zero monitor (checks if the analogue signal for 0% is at 4 mA and not at 0 mA (line break monitor)) and HART |
| E02010-00311000 | E02010-30312111 | Use IS version; alternative offers 2 trips - live zero monitor (checks if the analogue signal for 0% is at 4 mA and not at 0 mA (line break monitor)); DVM (Digital Volt Meter to adjust trip points and/or monitor signal) - HART |
| E02010-00311011 | E02010-30312111 | Use IS version; alternative offers 2 trips - live zero monitor (checks if the analogue signal for 0% is at 4 mA and not at 0 mA (line break monitor)); DVM (Digital Volt Meter to adjust trip points and/or monitor signal) - HART |
| E02010-10312110 | E02010-30312111 | Check Uo-Io (IS parameters may be different - please check); alternative offers HART |
| E02010-20312010 | E02010-30312111 | Alternative offers live zero monitor (checks if the analogue signal for 0% is at 4 mA and not at 0 mA (line break monitor)) and HART |
| E02010-20312100 | E02010-30312111 | Alternative offers DVM (Digital Volt Meter to adjust trip points and/or monitor signal) and HART |
| E02010-20312110 | E02010-30312111 | Check Uo-Io (IS parameters may be different - please check); alternative offers HART |
| E02010-20312110-S1 | E02010-30312111 | Add S1 - alternative offers HART |
| E02010-30311011 | E02010-30312111 | Alternative offers 1 relay - live zero monitor (checks if the analogue signal for 0% is at 4 mA and not at 0 mA (line break monitor)) |