Ampgard medium-voltage starters are the ultimate in motor control, performance, reliability and protection. Eaton offers a complete line of full voltage and reduced voltage starter types. This broad selection of medium-voltage control supports a wide range of industrial applications including pulp and paper, water and wastewater, oil and gas and HVAC.
View images of Ampgard 15 kV medium-voltage motor control
| POWER RATING | 100-7500 Hp |
| INPUT VOLTAGE RATING | 7200-13800 V |
| BASIC IMPULSE LEVEL (BIL) | 75 kV / 95 kV BIL |
| INTERRUPTING RATING | 50 kA rms symmetrical |
| AMBIENT TEMPERATURE | 0 to 40 degrees C |
| UL | 347 |
| NEMA | ICS3 |
| CSA | C22.2 |
| THIRD PARTY RECOGNITION/APPROVAL | UL/cUL available for most configurations |
| SEISMIC QUALIFICATION | IBC |
| ENCLOSURE TYPE |
NEMA 1, NEMA 12, NEMA 3R |
| ACCESSIBILITY |
Front |
| INDOOR SECTION DIMENSIONS (TYPICAL) |
36"w x 30"d x 92"h |
| BUS INSULATION | Heat shrink sleeve |
| BUS SUPPORTS | Glass polyester |
| SWITCHING DEVICE |
Vacuum contactor (300A) |
| CONTACTOR CONNECTION |
Stab |
| FUSE MOUNTING | Bolted |