Eaton’s substation-grade SMP distributed I/O platforms of the SMP IO-2000 series are specially designed to meet the requirements for distributed I/O in modern utility substation automation systems. This family of products is Linux-based and includes the evolutive SMP IO-2230 platform which supports binary inputs, binary outputs and analog inputs and the SMP IO-2330 system, with four models pre-mapped to specific I/O configurations. All models communicate over serial RS-485 or TCP/IP using fiber or copper Ethernet and can be integrated with the SMP Substation automation platform or used as standalone I/O modules that connect directly to a master station.
| Substation-grade | The SMP I/O is a robust substation-grade hardware platform that meets IEEE 1613 and IEC 61850-3 standards for vibration, electrical surges, fast transients and extreme temperature ranges. |
|---|---|
| Designed for growth | The SMP I/O input and output cards can be added in minutes, without removing the unit from the rack. |
| Seamless networking | The SMP I/O includes 1 Ethernet and 1 RS-485 port. It uses the industry-standard DNP3 protocol. |
| Reduced engineering effort | The SMP I/O saves on cabling, commissioning and configuration time, especially when it is used with the SMP Gateway. Its removable connectors speed up hardware changes. |
| Accurate data | The SMP I/O’s error-detection features ensure data integrity between the data point and the control center. It supports IRIG-B synchronization for precise timestamping. |
| General specifications | The SMP I/O is composed of a base unit that can accept up to four field-installable I/O cards. The base unit provides two programmable form-C output relays, RS-485 and Ethernet communications interfaces, and an IRIG-B interface. All wiring is on the rear panel through removable terminal blocks. The front panel displays the status of the device and the state of all I/O signals. A Local/Remote control disables all control commands from the master station for operator safety during system maintenance. |
|---|---|
| Dimensions | Rack-mount 1U 1.72 in. H x 19 in. W x 8 in. L 43.6 mm H 482.6 mm W x 203.2 mm L Wall-mount 4” H x 11.9” W x 6.85” L 101 mm H 302 mm W x 174 mm L |
| Power Supply | Low-voltage model Rated supply voltage: 24-48 VDC Input voltage range: 18-75 VDC High-voltage model Rated supply voltage: 110-250 VDC / 110-240 VAC Input voltage range: 100-300 VDC / 85-264 VAC Frequency range: 50/60 Hz |
| Communications | Ethernet 10/100BASE-TX, RJ-45 connector or 100BASE-FX, up to 2 km, LC connector, multimode 1300 nm RS-485 Multi-drop 2 wires, up to 1200 m (4000 ft.) and 32 devices Terminal blocks |
| Time Synchronization | IRIG-B Demodulated 2V high level detection, Vin max up to 12 VDC, Opto-isolated, Terminal blocks |
| Ports | 8 Independent opto-isolated ports per module with optional Error Detection Circuit (EDC) Input range: 24 VDC 48 VDC 110 VDC 125 VDC 220 VDC 250 VDC Current sink: EDC input option* 4 mA maximum Non-EDC input option* 2 mA maximum |
| Binary Inputs | Base unit: 2 programmable Form C relays Ports: 8 independant Form A relays per module Rating: 8 A at 250 VAC resistive 8 A at 30 VDC resistive 0.4 A at 125 VDC resistive 0.2 A at 150 VDC resistive ½ HP at 125 VAC, ¼ HP at 250 VAC |