The Eaton BladeUPS has reached end-of-life status. Eaton will, of course, continue to provide services and replacement parts for the BladeUPS. If you're looking for a replacement UPS, the Eaton 93PX 3Phase UPS is the replacement offering coming in late July 2025
The Eaton BladeUPS is a three-phase, scalable and modular UPS for high density computing environments, including virtualized or machine learning IT applications. The BladeUPS delivers 12 kW of efficient, reliable power in only 6U of rack space, including batteries. You can expand its capacity by combining 12 kW modules in a scalable, building block fashion to deliver 60 kW (N+1) from a single rack enclosure. This powerful configuration delivers higher power density than competitive, modular solutions while dissipating only one-third of the heat. By incorporating a BladeUPSs bus bar, you can easily self-install new paralleled units to keep up with your data center needs. While you can design a BladeUPS from scratch, you can also quickly deploy the Eaton BladeUPS Preassembled System, which is a turnkey solution featuring easy customization, shipping and installation. The BladeUPS can be easily monitored via the units’ brightly backlit LCD screen and through Eaton’s Intelligence Platform.
"Before Eaton's products we had APC stuff. In terms of the reasons we switched; capacity for the footprint was one, price was absolutely another and the scalability."
Matt Yorston, Data Center Manger at a consultancy
| Power rating | 5-60 kW |
|---|---|
| Voltage | 208 and 400 Vac models |
| Frequency | 50/60 Hz |
| Topology | Double conversion on demand |
| Efficiency | Up to 98% |
| Configuration | Rackmount |
| Input voltage | 208 and 400 Vac models |
|---|---|
| Voltage range | 208V models: 180 to 265 Vac 400V models: 311 to 500 Vac |
| Frequency range | 50 or 60 Hz, ±5 Hz |
| Input currency distortion | <5% with IT loads (PFC power supplies) |
| Input power factor | >0.99 with IT loads (PFC power supplies) |
| Inrush current | Load dependent in high efficiency (HE) mode; 100% in normal mode |
| Input requirements | Three-phase, four-wire + ground |
| Bypass source | Same as input (Single feed) |
| Generator compatibility | Fast sync slew rate for generator synchronization, programmable return to AC source delay |
| Rated output voltage | 208V models: 180 to 225 Vac, Ph to Ph 400V models: 180 to 240 Vac, Ph to N |
|---|---|
| Output configuration | Three-phase, four-wire + ground |
| Output frequency (nominal) | 50 to 60 Hz auto-detection on startup |
| Frequency regulation | 0.1 Hz free running |
| Load power factor range | Lagging: 0.7 Leading: 0.9 |
| Total output voltage distortion | <3% with IT loads (PFC power supplies) <5% non-linear or non-PFC power supplies |
| Battery type | VRLA-AGM |
|---|---|
| Battery string voltage | 240 Vdc |
| Battery test | Automatic battery test standard Remote scheduling capable Manual battery test from front display |
| Battery recharge profile | |
| Battery cut-off voltage | Variable from 1.67 VPC at <5 minute runtime to 1.75 VPC at >90 minute runtime |
| Battery low condition | Announced with alarm |
| Extended batteries | Up to four 3U battery enclosures |
| 50% loading | 100% loading | |
|---|---|---|
| Internal runtime | 8 kW: 23 minutes 12 kW: 13 minutes | 8 kW: 9 minutes 12 kW: 4.7 minutes |
| Extended battery capability | 8 kW: 120 minutes 12 kW: 76 minutes | 8 kW: 55 minutes 12 kW: 34 minutes |
| Height | Width | Depth | |
|---|---|---|---|
| UPS | 10.3 in/267 mm (6U) | 17.4 in/442 mm | 28.4 in/720 mm |
| EBM | 5.2 in/132 mm (3U) | 17.2 in/437 mm | 26 in/660 mm |
| Chassis weight without batteries or electronics | 80 lb/36 kg |
|---|---|
| Chassis weight with batteries and electronics | 307 lb/140 kg |
| UPS weight without batteries | 135 lb/61 kg |
| UPS weight with 2 strings of batteries | 307 lb/140 kg |
| UPS weight with 1 sting of batteries | 218 lb/99 kg (5 kW UPS only) |
| EBM shipping weight | 170 lb/77 kg |
| Heat dissipation (HE model) | 371 watts/1266 BTU/hr at 100% rated load (12 kW) 264 watts/903 BTU/hr at 100% rated load (8 kW) 210 watts/707 BTU/hr at 100% rated load (5 kW) |
|---|---|
| Cooling | Fan cooled, temperature microcomprocessor monitored Front air entry, rear exhaust |
| Audible noise, normal operation | <60 dBA at 1 meter |
| Altitude before derating | 1000 meters (3300 ft ASL) |
| Software compatibility | |
|---|---|
| X-slot bays | Two |
| Control panel LCD | Two lines by 20 characters Four menu-driven interface buttons Four status-at-a-glance LEDs |
| Multi-language | English standard 20 languages available |
| Configuration changes | User capable, firmware auto configures |
| Dry contact inputs | Two, user-configurable |
| Dry contact outputs | One, user-configurable |
| Installation | User capable, optional factory serivce available |
|---|---|
| Preventive maintenance | User capable, optional factory serivce available |
| Corrective maintenance | User capable, optional factory serivce available |
| Serviceability | Hot-swappable batteries Hot-swappable electronics modules Automated internal maintenance bypass Auto-configure firmware Flash firmware upgradeable |
| Safety | 208V models: UL1778, cUL 400V models: CE, EN 62040-1, EN 60950-1: 2006, cULus |
|---|---|
| EMI/EMC | 208V models: FCC Part 15 Class A EN 62040-2: 2006 |
| Surge protection | 208V ANSI C62.41, Cat B-3 EN 62000-4-5 |
| Additional ratings | EN 61000-3-2, EN 61000-3-3, EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6, EN 61000-4-8 |
| Hazardous materials (RoHS) | EU Directive 2002/95/EC |
| Standard | 18 months from date of shipment |
|---|---|
| Warranty repair | Factory depot repair or replace |
Support from Eaton