Function
|
Modbus / Facility Web/SNMP
|
UPS supported
|
5P, 5PX, 9PX, 9PXM, 9SX, 93PM, 93E, 9395XC
|
Catalog number
|
INDGW-M2
|
Part number
|
744-07774 |
Protocol support
|
HTTPS, TLS 1.2, SNMPv1, SNMPv3, NTP, TFTP, SMTP, SMTPS, BOOTP, DHCP, SLAAC, SSH, MQTTS, ModbusTCP, Modbus RTU, BACnet IP, BACnet BBMD |
UPS slot type
|
Mini-Slot
|
Network support
|
Ethernet 10/100/1000BaseT
|
| Temperature and humidity monitoring |
Yes, with environmental monitoring probe Gen 2 (catalog number: EMPDT1H1C2, part number: 744-A4026)
|
Software support
|
Intelligent power manager 1.61 and higher, intelligent power protector 1.61 and higher, any SNMP compliant network management system (NMS)
|
Supported MIB
|
MIB II – Standard IETF UPS MIB (RFC 1628) – Eaton xUPS MIB
|
O/S supported for shutdown |
Microsoft Windows, UNIX, and Linux
|
Local language support
|
English, French, German, Italian, Spanish, Chinese simplified, Chinese traditional, Japanese, Russian
|
Operating temperature
|
32 to 104°F (0 to 40°C)
|
Operating humidity
|
90% RH max. without condensation
|
| Power input |
5 to 12V
|
Current consumption
|
500/1000mA max. depending on UPS
|
Dimensions (H X W X D)
|
5.2 x 2.6 x 1.7 in. (132.08 x 66.04 x 43.18 mm)
|
Weight (OZ.)
|
2.5
|
Regulatory
|
Same as UPS
|