Eaton Tripp Lite series switched PDU, 1PH, 2U, NEMA L6-30 input, 15ft cord, 5.5kW, 24A, 208V, 14 outlets (8) C13 (6) C19
| Product Name |
Eaton Tripp Lite series switched PDU
|
| Catalog Number |
PDUMH30HV19NET
|
| UPC |
037332153753
|
| Product Length/Depth |
12.5 in
|
| Product Height |
3.5 in
|
| Product Width |
17.5 in
|
| Product Weight |
13.7 lb
|
| Compliances |
FCC Class A
RoHS |
| Certifications |
NOM
CSA certified UL 60950-1 |
| Form factor |
2U
|
| Package contents |
|
| Operating Temperature |
32° to 104°F (0° to 40°C)
|
| Mounting direction |
Horizontal
|
| Material |
Metal
|
| Input connection |
NEMA L6-30P
|
| Cord length |
15 ft
|
| Amperage Rating |
24A
|
| Electric current - max |
24
|
| Phase |
Single-phase
|
| Frequency rating |
50/60 Hz
|
| Number of Outputs C13 |
8
|
| Number of Outputs C19 |
6
|
| Features |
Flex Center
|
| SNMP |
Yes
|
| Front Panel LCD Display |
2 digit meter and pushbutton display toggle switch reports output current in amps in 3 loading segments, Bank 1 (C13 outlets #1-8), Bank 2 (C19 outlets #9-14) and Banks 1&2 combined (Outlets #1-14)
|
| Output Receptacles |
C13
C19 |
| Grounding options |
Grounding lug
|
| LED indicators |
14 power availability LEDs confirm power off/on status for each built-in outlet; Two additional LEDs identify which bank the visual current meter is reporting (Bank 1, Bank 2 or Banks 1&2 combined)
|
| Minimum required rack depth |
16 in
|
| Network ports |
RJ45 Network port, Micro-USB Configuration port, USB A port supports a variety of Envirosense2 environmental and control modules. See Accessories>Management Hardware section for more information about these modules.
|
| Overload protection |
Three 20A circuit breakers; Breaker 1 (Bank 1 C13 outlets #1-8), Breaker 2 (Bank 2 C19 outlets #9-11), Breaker 3 (Bank 2 C19 outlets #12-14)
|
| Recommended electrical service |
Single-phase 30A 208/230V service
|
| Output Receptacles Details |
Compatible with Eaton Tripp Lite Power Cords
|
| Receptacles |
|
| Input Cord Length |
15 ft
|
| Switch configuration |
Pushbutton near the two digit current meter toggles reporting of output amps on Bank 1, Bank 2 and Total PDU output (Banks 1 & 2 combined)
|
| Communications Cable |
Micro-USB- to-USB A configuration/console Access cable
|
| Amperage Rating Details |
Agency de-rated to 24A continuous
|
| Operating elevation |
0-10000 ft. (0-3000 m)
|
| Operating temperature range |
32° to 104°F (0° to 40°C)
|
| Output nominal voltage |
208/230V
|
| Relative humidity |
5% to 95% non-condensing
|
| Form Factors Supported |
2U rackmount
|
| Output Capacity Details |
5.5kW (230V), 5kW (208V) total capacity / 30A max (Agency de-rated to 24A), 20A max per breakered outlet bank; 16A max per C19 outlet; 12A max per C13 outlet
|
| Storage temperature |
-22° to 122°F (-30° to 50°C)
|
| Network Speed |
10 Mbps
100 Mbps (Fast Ethernet) |
| Product Highlights |
Federal Trade Agreements Act / TAA Compliant for GSA Schedule purchases
5.5kW 208/230V Switched 24A PDU, 2U rackmount, Reversible housing 14 Switched outlets (8 C13, 6 C19) and 15ft./4.5m NEMA L6-30P input cord Reports voltage, frequency and load level; Front-panel digital current meter Pre-installed WEBCARDLX with latest version of PADM20 for IP-based Auto Probe feature |
| PowerAlert Software |
LX Platform Interface: PowerAlert Device Manager
|
| SNMP Compatibility |
Pre-installed LX platform interface provides remote monitoring via Java-free HTML5 web interface, telnet, SSH and SNMP management systems
|
| PDU Plug Type |
NEMA L6-30P
L6-30P |
| PDU Type |
Switched
|
| PDU Input Voltage |
208
|
| High Availability PDU Features |
Auto probe monitoring and reboot (included)
Auto load shedding |
| PDU Form Factor |
Horizontal (2U)
|
Support from Eaton