900VA 480W Line-Interactive UPS with 6 Outlets - AVR, VS Series, 120V, 50/60 Hz, Tower
| Product Name |
Eaton Tripp Lite series UPS
|
| Catalog Number |
VS900T
|
| UPC |
037332212900
|
| Product Length/Depth |
13.7 in
|
| Product Height |
8.6 in
|
| Product Width |
5.3 in
|
| Product Weight |
12.6 lb
|
| Compliances |
FCC Class A
RoHS |
| Certifications |
NOM
UL 1778 CSA certified |
| Topology |
Line-interactive
|
| Form factor |
Tower
|
| Package contents |
|
| Input nominal voltage |
120 VAC
|
| Nominal frequency |
60 Hz
|
| Input frequency range |
60 Hz
|
| Receptacle |
5-15R
|
| Output nominal voltage |
110 / 120V
|
| Electric current - max |
|
| Battery type |
Valve Regulated Lead Acid (VRLA)
|
| Runtime at half load |
3.8 min
|
| Relative humidity |
0-90% non-condensing
|
| Output Receptacles |
5-15R
|
| Product Highlights |
AVR battery backup allows time to save files and safely shut down during blackouts
6 NEMA 5-15R outlets provide power to PC, home theater or digital signage equipment High 95% efficiency with low BTU ratings saves power and lowers your energy costs Alarm and front-panel LEDs report online, battery, fault and overload conditions Protects valuable equipment from dangers posed by brownouts, surges and line noise |
| Nominal Output Voltage |
110V
115V 120V |
| Network Management Cards Details |
Network management not supported
|
| Output power factor |
0.53
|
| Phase (input) |
Single-phase
|
| Runtime at full load |
0.5 min. (480W)
|
| Communication interface |
None
|
| Dc Voltage |
12
|
| Operating Temperature Range |
32° to 104°F (0° to 40°C)
|
| Input Circuit Breakers |
10A
|
| High Voltage Transfer to Battery Power |
145
|
| Low Voltage Transfer to Battery Power |
89
|
| Undervoltage Correction |
Input voltages between 89 and 108 are boosted by 18%
|
| Application |
|
| Switch configuration |
Controls off/on power status
|
| AC suppression joule rating |
316
|
| Housing material |
ABS
|
| Output AC waveform (AC mode) |
Sine wave
|
| Output AC waveform (battery mode) |
PWM sine wave
|
| Output Capacity (kVA) |
0.9
|
| Output Capacity (kW) |
0.48
|
| Output Capacity (VA) |
900
|
| Output Capacity Details |
7.5A @ 120V. (LINE MODE) 110%+/- 10% @ 5 minutes; (BATTERY MODE) 110% +/- 10% @ 5 seconds
|
| Primary UPS Depth (mm) |
300
|
| Primary UPS Height (mm) |
142
|
| Primary UPS Width (mm) |
102
|
| AC Suppression Response Time |
Instantaneous
|
| Audible Alarms |
Audible alarm indicates low-battery, fault, overload and replace-battery status
|
| LED Indicators |
3 LEDs indicate online mode (green), battery mode (yellow) and fault mode (red)
|
| Frequency Rating Details |
Output is regulated to +/-0.05Hz when input frequency exceeds +/-5Hz of nominal.
|
| Output Voltage Regulation (Line Mode) |
120V (+9%, -12%)
|
| Output Voltage Regulation(Battery Mode) |
120V (+/- 10%)
|
| Overvoltage Correction |
Input voltages between 132 and 145 are reduced by 15%
|
| Rechargeable Battery |
8 hours (10% to 90%)
|
| Recommended Electrical Service |
15A 120V
|
| Storage Temperature |
5° to 113°F (-15° to 45°C )
|
| Nominal Voltage Details |
120V sinusoidal in line mode and 120V PWM in battery mode
|
| Voltage Regulation Description |
Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 89 to 145
|
| Maximum Input Amps |
10
|
| UPS Input Cord Length (m) |
1.5
|
| UPS Power Module Dimensions |
5.6 x 4 x 11.8
|
| Power Mode Transfer Time |
6 milliseconds
|
| EMI AC Noise Suppression |
EMI / RFI AC Noise Suppression
|
| UPS Input Connection Type |
5-15P
|
| UPS Output Receptacles |
4 UPS outlets, 2 surge-only outlets
|
| High Availability UPS Features |
Automatic voltage regulation (AVR)
Surge/noise protection |
Support from Eaton